Go top
Conference paper information

Remote open phase faults in the start-up transformers of a nuclear power generating station

L. Rouco, J. Archilla Martín-Sanz, C. Gavilán

7th International Advanced Research Workshop on transformers - ARWtr 2022, Baiona (Spain). 23-26 octubre 2022


Summary:

United States Nuclear Regulatory Commission (US NRC) has requested to the US nuclear power generating industry that Open Phase Conditions (OPCs) should be automatically detected. This requirement has been extended by other regulatory bodies worldwide. Several systems for detecting OPCs are available in the marketplace. Remote open phase faults in the supply system of start-up transformers of nuclear power generating stations (NPGSs) pose a major challenge for available detection systems. A remote fault consists of an open phase fault in an intermediate point of the transmission line that feeds the startup transformer of the NPGS. This paper investigates the ability of existing methods to detect a remote open phase fault in the transmission line that feeds the start-up transformer of a NPGS.


Keywords: Open phase faults, Nuclear power generating stations, Unit Auxiliary transformer, Station start-up transformer, Symmetrical component analysis


DOI: DOI icon 10.23919/ARWtr54586.2022.9959934

Publication date: October 2022.



Citation:
Rouco, L., Archilla Martín-Sanz, J., Gavilán, C., Remote open phase faults in the start-up transformers of a nuclear power generating station, 7th International Advanced Research Workshop on transformers - ARWtr 2022, Baiona (Spain). 23-26 October 2022.

IIT-22-115C

Request Request the document to be emailed to you.