Go top
Conference paper information

The Role of Transmission to Distribution OLTC transformers in the Iberian Peninsula Blackout

A. Benítez Domínguez, E. Lobato, L. Rouco, I. Egido, F. Gegúndez Nogueroles, A. Pérez Guillén, P. Mancarella

2nd IEEE Power & Energy Society International Meeting - IEEE PES IM 2027, Beijing (China). 10-13 January 2027


Summary:

The Iberian Peninsula blackout on 28 April 2025 involved rapid voltage increases and cascading generation disconnections, triggered by overvoltage protections. A significant share of renewable generation, controlled by constant power factor, is embedded within distribution networks (DNets), which evacuate their output to the transmission network (TNet) via an on-load tap changer (OLTC) transformer that controls the low-voltage side voltage. The potential contribution of these OLTC transformers remains under discussion. This paper investigates the contribution of TNet-DNet OLTC transformers to the mechanism associated with overvoltage disconnections through a 6-bus test system that qualitatively reflects the operating state of the Iberian Peninsula prior to the blackout. A quasi-dynamic simulation is performed to reproduce the generation loss and show the effect of OLTC with tap-changing enabled. Results show that in generators with PQ control, the OLTC protects the DNet, with negligible effect on the TNet. However, for PV control, the OLTC can transiently increase voltage in the TNet. The relevance of this adverse behavior depends on the topology and operating point.


Spanish layman's summary:

Este paper estudia el papel de los transformadores con cambio de toma entre transporte y distribución en el apagón ibérico, analizando cómo las unidades renovables protegen distribución casi sin efecto en transporte, y cómo las convencionales tienen un efecto transitorio negativo en transporte.


English layman's summary:

This paper examines the role of transmission-to-distribution OLTC transformers during the Iberian blackout, analyzing how renewable units provide protection to the distribution grid with no impact on transmission, and how conventional units exert a negative transient effect on the transmission side.


Keywords: OLTC transformers, voltage collapse, voltage control


Publication date: 10-Jan-2027.


Citation:
A. Benítez Domínguez, E. Lobato, L. Rouco, I. Egido, F. Gegúndez Nogueroles, A. Pérez Guillén, P. Mancarella, "The Role of Transmission to Distribution OLTC transformers in the Iberian Peninsula Blackout", presented at 2nd IEEE Power & Energy Society International Meeting - IEEE PES IM 2027, Beijing, China, 10-13 January 2027

    Research topics:
  • Steady-state: Load flows, analysis of power system constraints, optimal load flows, voltage control ancilliary service,short-circuits, protections in transmission and ditribution networks
    Research groups:
  • Instituto de Investigación Tecnológica (IIT)
    ODS:
  • Goal 9: Industry, innovation and infrastructure

IIT-27-001C

Request Request the document to be emailed to you.