This paper presents a new method to model the steady state fault current contribution of inverter?connected generation such as type 4 wind and PV generators during three?phase shortcircuits.
The proposed method is based on the Norton equivalent of the generators. The method basically adds a resonant admittance to cancel out the impact of the equivalent admittance for
fault current computation. This way, iterative computations are avoided. The proposed method is simple to implement and it has been successfully applied to a simple and a real system
consisting of planned wind farm on the Canary Islands.
Fecha de Registro: 21/03/2018
IIT-18-027A
Debido a las restricciones de copyright existentes, no se puede distribuir este material vía web. Sin embargo, mediante este formulario puede contactar con los autores. Ellos podrán distribuir un número limitado de copias del mismo por correo electrónico. Por favor, comprueba tu carpeta de correo no deseado.