Ir arriba
Información del artículo

New on-line rotor ground fault location method for synchronous machines with static excitation

C.A. Platero, F. Blázquez, P. Frías, M. Pardo

This paper presents a novel on-line rotor ground fault location method for synchronous machines, which, combined with rotor ground fault protection, can detect and locate faults in the rotor. This method is suitable for synchronous machines with static excitation systems, whose excitation field winding is fed by rectifiers through an excitation transformer. The main contribution of this new technique is that it can locate the position of a ground fault in the rotor winding online, reducing the repair time. The proposed technique is based on the analysis of the ac and dc components of the excitation voltage and the voltage measured in a grounding resistance located in the neutral terminal of the excitation transformer. This technique has been validated through computer simulations and experimental laboratory tests.


Keywords: AC generator excitation, fault location, power generation protection, synchronous generator excitation.


IEEE Transactions on Energy Conversion. Volumen: 26 Numero: 2 Páginas: 572-580

Journal Impact Factor: JCR impact factor 3.767 (2017)

DOI reference: DOI icon 10.1109/TEC.2010.2095501    

Publicado en papel: Junio 2011.


    Líneas de investigación:

pdf  Previsualizar
pdf Solicitar el artículo completo a los autores



Aviso legal  |  Política de cookies |  Política de Privacidad

© Universidad Pontificia Comillas, Escuela Técnica Superior de Ingeniería - ICAI, Instituto de Investigación Tecnológica

Calle de Santa Cruz de Marcenado, 26 - 28015 Madrid, España - Tel: (+34) 91 5422 800