This paper investigates whether existing protection schemes would detect an open phase fault in the start-up power supply system of a 1092 MW Spanish nuclear power generating station. This investigation follows to the 2012 event at unit 2 of Byron station, Illinois, USA. Symmetrical components method is proposed to draw fundamental conclusions. The results of the symmetrical components analysis are validated using EMTP simulations.
Palabras clave: Open phase fault, nuclear power generating station, power supply systems, symmetrical components, EMTP simulation
6th International Advanced Research Workshop on transformers, Córdoba (España). 06 octubre 2019
Fecha de publicación: octubre 2019.
Cita:
L. Rouco, J. Archilla Martín-Sanz, C. Gavilán, Open phase faults in the start-up power supply system of a nuclear power generating station, 6th International Advanced Research Workshop on transformers - ARWtr 2019. ISBN: 978-84-09-11168-8, pp. 1-6, Córdoba, España, 06-09 Octubre 2019
IIT-19-083A