Ir arriba
Información del artículo en conferencia

A high frequency power transformers model for network studies and tdsf monitoring

X.M. López-Fernández, L. Rouco, C. Álvarez-Mariño, H. Gago, C. Vila

47 CIGRE Session - CIGRE 2018, París (Francia). 26-31 agosto 2018


Resumen:
In this paper a high frequency power transformer model for network studies is presented. The model combines white and black box representations in a package implemented as “compiled foreign model” of MODELS language of EMTP/ATP program. This approach allows modelling all network components in EMTP/ATP environment. The time domain severity factor (TDSF) monitoring is integrated into the white+black box model package, which offers valuable information to figure out the risk level supported by inner points of power transformer windings when the unit interacts with the network during fast transient conditions. The proposed white+black box model of a 50/50/16.67 MVA transformer is illustrated while simulating the lightning overvoltages when it is connected to a 220 kV gas insulated substation (GIS).


Palabras clave: High frequency modelling, Power transformers, Network studies, Time Domain Severity Factor.


Fecha de publicación: agosto 2018.



Cita:
López-Fernández, X.M., Rouco, L., Álvarez-Mariño, C., Gago, H., Vila, C., A high frequency power transformers model for network studies and tdsf monitoring, 47 CIGRE Session - CIGRE 2018, París (Francia). 26-31 agosto 2018.

IIT-18-040A

pdf Solicitar el artículo completo a los autores