Open phase faults in the external power supply systems of a nuclear power generating station: symmetrical components analysis and EMTP validation

L. Rouco, A. Pontes Jiménez, J. Archilla Martín-Sanz

This paper investigates whether existing protection schemes would detect an open phase fault in the power supply systems of a 1092 MW Spanish nuclear power generating station. This investigation follows to the 2012 event at unit 2 of Byron station, Illinois, USA. Symmetrical components method is proposed to draw fundamental conclusions. The results of the symmetrical components analysis are validated using EMTP simulations.


Palabras clave: Open phase fault, nuclear power generating station, power supply systems, symmetrical components, EMTP simulation

IEEE Power & Energy Society General Meeting - IEEE PES GM 2015, Denver, Colorado (Estados Unidos de América). 26-30 Julio 2015

Fecha de publicación: julio 2015.



Cita:
L. Rouco, A. Pontes Jiménez, J. Archilla Martín-Sanz, Open phase faults in the external power supply systems of a nuclear power generating station: symmetrical components analysis and EMTP validation, IEEE Power & Energy Society General Meeting - IEEE PES GM 2015. Denver, Estados Unidos de América, 26-30 Julio 2015